Schematic of a direct vented plumbing fixture (C) Carson Dunlop AssociatesPlumbing Vent Distances & Routing Codes

  • Mail service a QUESTION or Comment nearly plumbing vent pipe and systems: code, installation, distances, sizes

InspectAPedia tolerates no conflicts of interest. Nosotros have no relationship with advertisers, products, or services discussed at this website.


Plumbing vent distances, routing, clearances:

This article gives recommended or commanded distances from plumbing vent to fixtures, distances from plumbing vent to building features similar chimneys, windows, roofs, walls.

This article series includes definitions of plumbing vent terms, types of plumbing vents, plumbing vent size requirements, plumbing vent clearance distances to building roof, vertical walls, nearby windows, or plumbing vent distance to chimneys.

We explain how plumbing vents work on buildings, why plumbing vent piping is needed, and what happens to the building drains when the vent piping is not working.

Nosotros also provide an Commodity Alphabetize for this topic, or you can try the page top or lesser SEARCH BOX as a quick fashion to find information yous need.

Plumbing Vent Organization Distances & Routing

Plumbing vent terminology sketch (C) Carson Dunlop Associates The basic plumbing vent terms are shown in the sketch.

In these notes, the plumbing stack vents and other sketches included below are provided courtesy of Carson Dunlop Associates.

[Click to overstate whatever image]

Article Contents

  • PLUMBING VENT DISTANCES & ROUTING
    • Distance: PLUMBING FIXTURE to VENT Pipage STACK
    • DRAIN & VENT SIZE & DISTANCES to FIXTURES
    • ROUTING SPECS for PLUMBING VENTS
    • VENT Altitude to BUILDING FEATURES
    • VENT CLEARANCE DISTANCE CODES

Basically, larger piping diameter allows longer distances betwixt a plumbing fixture and its vent stack. If a plumbing fixture is located too far from the principal building vent stack, and then its own drain pipe must have its own vent stack connection pipage.

The usual slope on the fixture drain pipe is 1/4" of slope per 12" (foot) of horizontal distance or "run" of piping.

Distances: How far tin the plumbing vent piping be located from a plumbing fixture?

Schematic sketch of distance allowed between a plumging fixture and vent piping (C) Carson Dunlop Associates

As we hash out at PLUMBING DRAIN Dissonance DIAGNOSIS, if the horizontal altitude between a plumbing fixture and the vertical vent piping is too peachy, the fixture may not drain properly, producing wearisome drainage or gurgling noises.

Poor drainage is non just an annoyance, it tin can exist dangerous since there is too the gamble that the poorly vented plumbing fixture volition lose the water from its plumbing trap, so permitting sewer gases into the edifice.

Every bit we show in Carson Dunlop Associates' sketch, the distance allowed between a plumbing fixture (really the fixture plumbing trap) and the vertical vent piping varies between a minimum and maximum as a part of the piping diameter.

Tables of Plumbing Drain Pipe & Vent Pipe Sizes (1) and Disquisitional Distances to Plumbing Fixtures (ii)

Beneath, our Tables 1 and 2 summarize common plumbing code specifications for fixture venting and vent pipe sizes and distances that a plumbing fixture tin be located (horizontally) from the vent stack. You'll see these distances also in our sketch at left. [Click whatever image to meet an enlarged, detailed version.]

Table i. Plumbing Drain Pipe Sizes
Drain Pipage Diameter Vertical Bleed Pipe, Maximum Number of Fixtures Horizontal Drain, Maximum Number of Fixtures
one-one/four" dia 1 1
one-1/2" dia 2 1 (or 2 sinks)
2" diam 16 8
ii-1/ii" dia 32 14
3" diam 48 35
four" diam 256 216

Notes to Table 1 above

Annotation: you can meet from this table that at common habitation bleed pipe sizes, if your pipage is two" or larger y'all're unlikely to run into drain chapters problem.

Table two. Vent Pipe Distances
Bleed Pipe Size Vent Pipe Size[one] Distance [2]
1-1/four" diam 1-ane/4" diam 2-1/two feet
1-1/two" diam one-one/4" diam 3-1/2 feet
ii" diam i-i/2" diam 5 feet
3" diam 2" diam 6 anxiety
4" diam 3" diam 10 feet

Notes to Table 2 above

[i] Minimum bore of the vent pipe

[2] Critical distance betwixt the plumbing fixture and the vent pipage. You lot can meet that for vent pipage diameters under iv" you lot demand to be vigilant about not locating a plumbing fixture too far from its vent piping/stack

Plumbing Vent Routing Specifications

Inside the building, the plumbing vent routing is generally unrestricted.

That is, dry vent pipage carrying but air, sewer gas, or moisture to above the roof line is unrestricted. Nevertheless the pipe does need to be protected from nails - use nail plates to protect vent and drain pipage both where where pipage passes through studs, joists, or rafters.

Special routing and connections are required for proper venting of plumbing fixtures such as kitchen isle or peninsula sinks or dishwashers - plumbing fixtures that are located where a straight vertical vent stack connectedness is not possible.

See ISLAND SINK PLUMBING VENTS for details.

Table of Plumbing Vent Clearance Distances to Building Features

The tabular array below gives required clearance distances to diverse building features and cites pertinent model plumbing codes.

Edifice Characteristic

Required Distance from Plumbing Vent Termination to Building Characteristic

Comments

Roof Surface, distance to Plumbing Vent 6 inches higher up nearest roof surface "nearest" accommodates sloped roof - i.e. measure from the "up-roof" side
Nearest vertical surface, distance to plumbing vent 12 inches from nearest vertical surface such as the side wall of an upper story on the building

Nearest window, door, opening, air intake, or ventilation shaft: distance to plumbing vent.

10 ft (120 inches) from nearest window, measured horizontally

- OR two ft. (24 inches) higher up nearest window [or other opening listed at left], measured vertically

We interpret this rule to apply to the required separation distances between a plumbing vent and nearest chimney on the building - Ed.

Notes to the tabular array above

Distances are measured horizontally unless we indicate otherwise

Plumbing Lawmaking Citations for Plumbing Vent or Vent Stack Clearance Distances

Quoting the IRC model plumbing code

12.4 VENT TERMINALS

12.four.i Extension Above Roofs

Vent pipes shall cease not less than 6 inches in a higher place the roof, measured from the highest point where the vent intersects the roof. EXCEPTION: Where a roof is used for any purpose other than weather protection, vents shall extend at least 7 anxiety to a higher place the roof and shall be properly supported.

12.four.4 Location of Vent Terminal

a. Vent terminals shall not be located where vapors tin can enter the building.

b. No vent terminal shall be located straight beneath any door, window, or other ventilating opening of a building or of another building,

nor shall whatever such vent final be within 10 anxiety horizontally of such opening unless it is at least 2 feet above the top of such opening.

c. Where a vent terminal is within 10 feet horizontally and less than 2 anxiety above a ventilation opening described in Section 12.4.4b

and the line-of-sight from the vent terminal to the ventilation opening is interrupted by the continuous ridge of a roof, the ridge shall be at to the lowest degree ii feet above the top of the opening. Otherwise, the vent last shall comply with Department 12.four.4b.

d. Where a vent terminal is within 10 anxiety horizontally and less than 2 feet above a ventilation opening described in Section 12.4.4b and the line of sight from the vent terminal to such ventilation opening is interrupted past a solid wall or solid barrier, the meridian of the wall or barrier shall be at least 2 feet above the top of the ventilation opening

and the shortest travel distance around the wall or barrier from the vent concluding to the nearest border of the ventilation opening shall be at least 10 anxiety. Otherwise, the vent last shall comply with Section 12.iv.4b.

Plumbing Code full-text on Plumbing Vent Codes

  • ICC Affiliate 9, Vents 2012 [PDF] complete text, original source: Maryland plumbing code, https://constabulary.resources.org/pub/the states/code/ibr/icc.ipc.2012.pdf

Code Citations for Plumbing Vent Terminals at the Rooftop or Through Walls

904.1 Roof extension. All open vent pipes that extend through a roof shall be terminated at least [NUMBER - typically 6 ] inches (mm) above the roof, except that where a roof is to be used for whatever purpose other than weather protection, the vent extensions shall be run at to the lowest degree 7 feet (2134 mm) above the roof.

904.2 Frost closure. Where the 97.5-percent value for outside design temperature is 0ºF (-18ºC) or less, every vent extension through a roof or wall shall be a minimum of 3 inches (76 mm) in diameter. Whatever increment in the size of the vent shall be fabricated inside the construction a minimum of 1 foot (305 mm) below the roof or within the wall.

904.iii Flashings. The juncture of each vent pipe with the roof line shall be made water tight by an approved flashing.

904.4 Prohibited employ.Vent terminals shall non be used every bit a flag pole or to back up flag poles, television aerials or similar items, except when the piping has been anchored in an approved manner.

904.five Location of vent terminal. An open vent terminal from a drainage system shall not exist located directly beneath any door, openable window, or other air intake opening of the building or of an adjacent building,

and any such vent concluding shall non be inside ten anxiety (3048 mm) horizontally of such an opening unless information technology is at least two feet (610 mm) to a higher place the top of such opening.

904.6 Extension through the wall. Vent terminals extending through the wall shall terminate a minimum of 10 feet (3048 mm) from the lot line and 10 anxiety (3048 mm) above boilerplate ground level. Vent terminals shall not terminate under the overhang of a structure with soffit vents.

Side wall vent terminals shall be protected to prevent birds or rodents from entering or blocking the vent opening.

904.7 Extension outside a structure. In climates where the 97.v-percent value for outside design temperature is less than 0ºF (-18ºC), vent pipes installed on the outside of the structure shall be protected against freezing by insulation, heat or both.

Plumbing Codes, Citations, Fulltext Codes, & Plumbing Code References

Watch out: while the 2015 IPC is the about-recent version of the International Plumbing Code, the 2018 IPC is under development. To understand which generation of the model building lawmaking or plumbing code applies to your specific projection y'all will need to cheque with your local building official. For example many jurisdictions are on the 2012 IPC or notwithstanding older versions.

  • International Code Council, 500 New Bailiwick of jersey Avenue, NW, sixth Floor, Washington, DC 20001 Tel: 1-888-ICC-SAFE (422-7233); Fax: (202) 783-2348 International: (202) 370-1800, Email: webmaster@iccsafe.org, Website: iccsafe.org
    Excerpt describing the IPC - International Plumbing Code

    The International Plumbing Code (IPC) is a proven, comprehensive model plumbing code that works seamlessly with ICC's family of building codes. It sets minimum regulations for plumbing systems and components to protect life, health and prophylactic of building occupants and the public.

    The IPC is available for adoption by jurisdictions ranging from states to towns, and is currently adopted on the state or local level in 35 states in the U.South. The IPC is built on the proven legacy of the BOCA National Plumbing Lawmaking, SBCCI Standard Plumbing Code, and ICBO Plumbing Lawmaking.

    The IPC sets minimum regulations for plumbing systems using both prescriptive and functioning-related provisions ...

    Buy the 2015 International Plumbing Lawmaking at this ICC page: http://shop.iccsafe.org/codes/2015-international-codes-and-references/2015-international-plumbing-coder.html

  • 2012 IPC International Plumbing Code, complete text, [PDF] retrieved 2016/08/11, original source: https://law.resource.org/pub/us/code/ibr/icc.ipc.2012.pdf, as adopted past the U.S. State of Code Maryland Administrative Regulations department 05.02.01.02
    This public document is the entire 2012 Plumbing Code
  • 2009 IPC ICC International Plumbing Lawmaking, [PDF] full text, retrieved 2016/08/11, original source: https://constabulary.resource.org/pub/us/code/ibr/icc.ipc.2009.pdf every bit adopted and incorporated by various U.Southward. states including Alabama, Colorado, Delaware, Florida, Michigan, New Hampshire, Due north Carolina, Ohio, Oklahoma, Pennsylvania, Rhode Island, Utah, Vermont, Virginia, Due west Virginia, and others.
  • 2006 IPC ICC International Plumbing Code, [PDF] full text, retrieved 2016/08/11, original source: https://law.resource.org/pub/u.s.a./code/ibr/icc.ipc.2006.pdf as adopted past various U.S. states and municipalities including Arizona, Arkansas, District of Columbia, Georgia, New York, Due south Carolina, and others.
  • 2006 IPC Chapter 9, Vents, 2006 Compatible Plumbing Code, [PDF] complete text as adopted by the Virgina 2006 Plumbing Code
  • 2000 IPC Chapter 9, Vents, 2000 Uniform Plumbing Code, [PDF] fulltext on plumbing vents, as adopted past the state of Louisiana
  • International Residential Code (IRC), for 1 and Two Family unit Dwellings, 2012 (Starting time Printing)
    Home Page: http://publicecodes.citation.com/icod/irc/index.htm
    Citation Page:
    http://publicecodes.citation.com/icod/irc/2012/icod_irc_2012_31_sec003.htm
  • International Mechanical Lawmaking (IMC), International Lawmaking Council [888] 422-7233, Op. Cit.
  • International Plumbing Lawmaking (IPC) (see NPC below), Op. Cit.
  • National Standard Plumbing Code, (NPC), 2009
    obtained From: National Assoc. of Plumbing-Heating-Cooling Contractors in New Jersey at [800] 652-7422 or NAPHCC [800] 533-7694,
    [As cited by New Bailiwick of jersey Country Department of Community Diplomacy]
    http://world wide web.land.nj.us/dca/divisions/codes/codreg/pdf_misc_codes/2006_nspc.pdf
  • New Jersey State Section of Community Affairs, Website: http://www.state.nj.us/dca/divisions/codes/codreg/

Reader Comments & Q&A

@Scott,

We have a two-part answer:

1. if the pipe violates the unit's required working space clearance distances (as in its installation / operation manual) that's a business organisation and those distances will due east in the transmission

2. No plumbing pipe, along its length, would be expected to exist an aroma source; an HVAC arrangement can't suck sewer gases through the sides or properly-made fittings of any pipe material (iron, plastic, copper, cast iron, etc).

Just IF there is an opening in plumbing within a edifice and nigh an air handler, such equally an open up-cleanout access or dry plumbing trap, those defects need to be corrected. That's not a distance issue it'due south an improper plumbing condition issue.

3. If you are asking about a rooftop plumbing vent too close to a mechanical organization air intake, the x pes rule probably applies.

If I've misunderstood the question, exercise assist me out here. Perhaps you can mail service a photo of the situation.

I have a customer who has an HVAC unit correct side by side to a 2" plumbing pipage which is bringing in the smell from the pipe. What is the proper distance the pipe should be from the unit.

@John GREEN,

Thank you for a helpful question on proper drainage for evaporative cooling systems.

We discuss Evaporative Coolers at SWAMP COOLERS

where nosotros include some evaporative cooler installation manuals.

Y'all'll run across that the drain pipe for evaporative coolers, in the model edifice codes, is treated the same as air conditioner condensate piping: the same rules apply, including avoiding a connection to sewer piping or vents, probably for the very concern that you raise.

Details are at CONDENSATE DRAINS, CODES
where we include

LOCATIONS for CONDENSATE DISPOSAL - proper locations

PLUMBING CODE for CONDENSATE DRAINS - code citations

Typical IO transmission language for evaporative coolers often ducks this trouble and volition simply refer you to local codes or officials for bleed pipage rules;

An example manual might state simply

Never drain the cooler onto the roof. Connect a hose from the
drain plumbing fixtures to a drain or gutter. H2o residue could stain the
roof or cause y'all to slip.

Bleed h2o from the overflow/bleed outlet must be carried away
through a pipe to a suitable discharge signal on the building or
belongings .(Co-ordinate to Local Regulation)

Question; a neighbor had a rooftop evaporator libation professionaly installed a few years ago. The Drain was routed to the sewer vent pipe just plopped in the superlative, about a 20 foot run, instead of the gutter or ground. Now isn't that similar pipeing in sewer gas to the living area?

They both had a bout with cv19 which is prevelent with waste materials. This seems counter objective to wellness and rubber. Any advice?

@Blake,

Thank you for the follow-up, it sounds as if you are on top of the question.

Do let us know if y'all encounter problem or if later on y'all call back there's a trouble with a drain, equally at that place are ofttimes other solutions.

Thank you so much. I calculated the TOTAL DFUs equally fourteen. I program to vent the washer and utility sink separately on the opposite end of the firm; they will flow into a 3-inch pipe. The kitchen sink will connect to that same 3-inch pipage, and that pipe volition and so pick up the tub before information technology hits the combo wye in the diagram.

Plus, the bath sink is already vented separately (probably into the attic, but that's another project), and then I think I should be good.

@Blake,

Thanks for the question and prissy sketch.

On the page higher up you'll see that when the drain is 3" bore your fixture (tub) tin exist upward to six feet from the vent.

In your sketch and GUESSING from your drawing equally not all distances are given, your tub is about 70 inches from the "truthful vent" - or simply under vi ft.

And then on that score you're ok.

But y'all need to add up all of the fixtures being vented - converting them into DFUs

(explained at PLUMBING Bleed FIXTURE UNITS DFUs)

and so check the full DFUs against your vent system.

In sum, when sizing vents we have to consider both distances (fixture to vent) AND full number of fixtures being vented; wyes, bends, etc. add equivalent DFUs to be sure that the vent will work.

Hello.
I'm redoing the plumbing in my disaster/house, and I continue second-guessing myself nigh venting the bathtub. Can yous take a look at this diagram and tell me if this looks up to code?

I basically want to know if I need to add an additional vent arm to the section in crimson. (The diagram is supposed to be as if you are looking down at the waste material pipes from above.)
Thank you in advance for your time and consideration!

@Trevor melt,

All of our clearance distances - a huge library - are

at CLEARANCE DISTANCES for BUILDING SYSTEMS & FEATURES

and as well therein we see

ELECTRICAL SERVICE WIRE CLEARANCES - clearances to edifice roof, windows, other features

That's the best guide.

Nosotros won't find every possible building detail listed; instead the code inspector would use her judgement.

For example, a plumbing vent that's metal ought to respect the almost careful or greatest roof-to-wire altitude: you'll encounter in this Carson Dunlop Assoc. sketch the distance over roof depends on whether the roof is sloped or flat .

How close can the vent be to the residential service on the roof?

@Steve,

yes only ... exist sure to wait at piping diameters an the DFU (Drain Fixture Unit) equivalent totals that y'all have to add when putting more sanitary (gradual) 90s into a vent organisation, to be sure that the system diameter and so chapters remain acceptable

Tin can you utilise 90s in a horizontal plumbing route for a second story bath routing around a chimney from a vertical stack

Wet

Encounter the venting distances given above.

Hello,

Building my basement and planning to install a moisture bar. Closest vent from where i am planning to install the sink is near 40ft. Tin i run a 40ft. Horizontal 2" PVC and connect it to the main vent? Is that permitted by code?

Thanks..

Rich:

In addition to a P-trap at each fixture, ask your local building inspector if she will accept air-admittance valves, aka vacuum-breaker V-200 type vents that are installed at the fixtures.

See AIR Admittance VALVES AAVs https://inspectapedia.com/plumbing/Air_Admittance_Studor_Vents.php also chosen Studor Vents

Adding a basement bathroom. The 3 inch mainline under the slab is less than 1 human foot from the fixtures. Can I driblet each fixtures plumbing line directly to the mainline without the need of boosted venting? Of course p traps volition be installed on the tub and sink.

The plumbing runs are very short to the mainline and without maneuvering additional pipe to accommodate a vent, would not fit. Practise I need to locate a vent on the mainline upstream near the fixtures? Cheers for whatsoever advice.

Jane,

Spotter out: Routing plumbing drains to spill into a toilet tank or bowl is not plumbing according to whatsoever model plumbing code nor is it a sensible practice.

Worse it advise such an amateur and in my opinion incompetent approach to building plumbing that I worry what other unsanitary or dangerous work has been done at such a property.

It is also a violation to spill sewage or graywater onto the ground.

The mobile abode that I bought, has a big sewer issue. Is it legal to bleed all pipes into the toilet? I have a video of running my washing machine & soap is coming out underneath the trailer where the toilet is. Thank you.

Marker

The requirement for 3 in bore or larger Plumbing vents depends on the plumbing codes that have been adopted where you live a country and city, and besides probably the age of the work.

Instance it was mutual in older buildings to utilize a smaller-diameter vent peculiarly when the just fixture is existence vented where a sink.

Do all vents running in the attic have to be iii inch

...

Continue reading at PLUMBING VENT DEFINITIONS, TYPES or select a topic from the closely-related articles below, or see the complete Article Alphabetize.

Or see these

Recommended Articles

  • AIR ADMITTANCE VALVES AAVs - Studor Vents Explained
  • PLUMBING Drain FIXTURE UNITS DFUs - drain fixture units or DFUs defined & explained + tabular array of DFUs
  • PLUMBING VENT DEFECTS & NOISES - dwelling
  • PLUMBING VENT CODES - code sources
  • PLUMBING VENT DISTANCES & ROUTING
    • DISTANCE: PLUMBING FIXTURE to VENT Piping STACK
    • DRAIN & VENT SIZE & DISTANCES to FIXTURES
    • ROUTING SPECS for PLUMBING VENTS
    • VENT DISTANCE to BUILDING FEATURES
    • VENT CLEARANCE Altitude CODES

Suggested citation for this web folio

PLUMBING VENT DISTANCES & ROUTING at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention communication.

Or see this

Index to RELATED ARTICLES: ARTICLE Index to PLUMBING SYSTEMS

Or utilise the SEARCH BOX found below to Enquire a Question or Search InspectApedia


...

Ask a Question or Search InspectApedia

Try the search box merely below, or if you adopt, mail a question or comment in the Comments box below and we volition respond promptly.

Search the InspectApedia website

Annotation: appearance of your Comment below may exist delayed: if your comment contains an image, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher InspectApedia.com - Daniel Friedman

Source: https://inspectapedia.com/plumbing/Plumbing-Vent-Distance-Codes.php